Sadhana Heavy Duty Ventilated Cable Tray
Schedule of Permissible Loads |
All figures given represent the maximum permissible uniformly distributed load in lbs, per foot run.Unsupported
Free Plan
SIZE |
2 Ft. |
4 Ft. |
6 Ft. |
8 Ft. |
16 Ft. |
4" x 16 BG x 2" |
960 |
238 |
105 |
58.4 |
13.3 |
6" x 16 BG x 2" |
979 |
243 |
107 |
59.0 |
13.0 |
9" x 16 BG x 2" |
1006 |
249 |
109 |
60.0 |
12.8 |
12" x 16 BG x 2" |
1034 |
255 |
111 |
61.3 |
12.6 |
15" x 14 BG x 2" |
1312 |
324 |
141 |
77.9 |
15.8 |
18" x 14 BG x 2" |
1314 |
324 |
141 |
74.3 |
14.1 |
24" x 14 BG x 2" |
1318 |
323 |
140 |
74.1 |
13.4 |
12" x 14 BG x 21/2" |
1798 |
446 |
195 |
108.0 |
23.3 |
15" x 14 BG x 21/2" |
1802 |
446 |
195 |
108.3 |
22.6 |
18" x 14 BG x 21/2" |
1805 |
446 |
194 |
106.7 |
21.8 |
24" x 14 BG x 21/2" |
1811 |
446 |
194 |
105.5 |
20.3 |
30" x 14 BG x 21/2" |
1817 |
447 |
193 |
104.5 |
18.9 |
36" x 14 BG x 21/2" |
1823 |
448 |
193 |
103.2 |
17.4 |
24" x 14 BG x 3" |
2343 |
578 |
253 |
138.6 |
28.3 |
30" x 14 BG x 3" |
2358 |
583 |
253 |
137.6 |
26.5 |
36" x 14 BG x 3" |
2373 |
587 |
254 |
137.6 |
25.8 |
(A) The maximum permissible point laod at-mid-span may be obtained from the formula
P = 1/2 x U x Swhere
;
P = Maximum permissible point load in lbs, at mid-span
U = Maximum permissible uniformly distributed load in lbs, per foot run
S = the particular free span in feet
(B) In case of a span not listed above, the corresponding maximum permissible uniformly distributed load may be found from the formula :
U
= 4 x (U at 2 ft. span) / S2
(C)
Free span exceeding 16 ft. are not recommended
TO CONVERT LBS / FOOT RUN LOAD INTO KGS / MTR MULTIPLY BY 138 |
Heavy Duty Extra Ventilated Cable Tray Type S.E.C.2
Group | Sadhana Engineering Corporation | Steelite Engineering Limited
Dew-Pond
Cooling Towers Pvt. Ltd. | Sadhana Castings Pvt. Ltd.(C)